Fault detection and elimination, Fault messages – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 137

Advertising
background image

Fault detection and elimination

Fault messages

U

EDK82MV222 DE/EN/FR 9.0

NPT

L

Remedy

Cause

Fault

PC

1)

Keypad

C0119 1 or 4)

No PTC connected

Connect PTC or switch off

monitoring

OH4

54

Controller

overtemperature

Controller too hot inside

z

Reduce controller load

z

Improve cooling

z

Check fan in the controller

OH51

203

PTC monitoring
(Display when

C0119 = 2 or 5)

Motor too hot due to

impermissibly high currents or

frequent and too long

acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off

monitoring

OU

-

DC bus

overvoltage
(Message or TRIP

configurable in

C0310)

Mains voltage too high

Check supply voltage

OUE

22

Braking operation

z

Increase deceleration times

z

When operating with an

external brake resistor:
– Check dimensioning,

connection and supply cable

of the brake resistor

– Increase deceleration times

Earth leakage on the motor

side

Check motor supply cable and

motor for earth fault (disconnect

motor from the inverter)

Pr

75

Faulty parameter

transmission

when using the

keypad

All parameter sets are

defective

Before enabling the controller,

repeat the data transfer or load

the Lenze setting

Pr1

72

Faulty PAR1

transfer with

keypad

Parameter set 1 is defective

Pr2

73

Faulty PAR2

transfer with

keypad

Parameter set 2 is defective

Pr3

77

Faulty PAR3

transfer with

keypad

Parameter set 3 is defective

Pr4

78

Faulty PAR4

transfer with

keypad

Parameter set 4 is defective

Pr5

79

Internal fault

EEPROM is defective

Contact Lenze

Pt5

81

Time error during

parameter set

transfer

Data flow from keypad or PC

interrupted, e.g. because

keypad was disconnected

during transfer

Before enabling the controller,

repeat the data transfer or load

the Lenze setting.