T

Commissioning

The most important codes for commissioning

EDK82MV222 DE/EN/FR 9.0

L

NOO

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0002*

uSEr

(cont.)

Saving of own

settings

9

PAR1

Ö

Own settings

You can save your own basic

settings for a controller (e.g.

machine delivery status):
1. Ensure that parameter set

1 is active

2. Controller inhibit
3. Set C0003 = 3,

acknowledge with 

4. Set C0002 = 9,

acknowledge with , to

save your own basic

settings

5. Set C0003 = 1,

acknowledge with 

6. Enable the controller.

C0002*

uSEr

(cont.)

Loading/copyi

ng of your

own basic

settings

Using this function, PAR1 can

be copied to parameter sets

PAR2 ... PAR4

5

Own settings

Ö

PAR1

Restorage of own basic

setting in the selected

parameter set

6

Own settings

Ö

PAR2

7

Own settings

Ö

PAR3

8

Own settings

Ö

PAR4

C0003*

Non-volatile

parameter

saving

1

0

Parameter not saved in EEPROM

Data loss after mains

disconnection

1

Parameter always saved in

EEPROM

z

Active after every mains

connection

z

Cyclic parameter changes

via bus module are not

allowed.

3

Own settings saved in EEPROM

Subsequently save parameter

set 1 as own basic setting

with C0002 = 9