Fault detection and elimination, Fault messages – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 135

Advertising
background image

Fault detection and elimination

Fault messages

U

EDK82MV222 DE/EN/FR 9.0

NPR

L

Remedy

Cause

Fault

PC

1)

Keypad

ce6

67

System bus (CAN)

function module

on FIF has the

”Warning” or

”BUS-OFF” status
(configurable in

C0126)

CAN controller signals

”Warning” or ”BUS-OFF”

status

z

Check whether bus termination

is available

z

Check shielding of the cables

z

Check PE connection

z

Check bus load, reduce the

baud rate, if necessary

ce7

68

Communication

error in case of

remote

parameterisation

via the system

bus (C0370)
(configurable in

C0126)

Node does not respond or is

not available

z

Check whether bus termination

is available

z

Check shielding of the cables

z

Check PE connection

z

Check bus load, reduce the

baud rate, if necessary

When operating with

Application I/O:
Parameter set change-over

has been parameterised

incorrectly

In all parameter sets, the ”change

over parameter set” signal

(C0410/13, C0410/14) must be

connected with the same source

EEr

91

External fault

(TRIP-SET)

A digital signal assigned to the

TRIP-set function is activated

Check external encoder

ErP0
...
ErP19

-

Communication

abort between

keypad and

standard device

Various

Contact Lenze

FAn1

95

Fan failure
(only 8200 motec

3 ... 7.5 kW)
TRIP or warning

configurable in

C0608

Fan is defective

Replace fan

FAn1

-

Fan is not connected

Connect fan
Check wiring

H05

105

Internal fault

Contact Lenze

id1

140

Faulty parameter

identification

Motor is not connected

Connect motor

LP1

32

Error in motor

phase
(Display when

C0597 = 1)

z

Failure of one/several

motor phases

z

Motor current too low

z

Check motor supply cables

z

Check U

min

boost,

z

Connect motor with a

corresponding power or adapt

motor with C0599

LP1

182

Error in motor

phase
(Display when

C0597 = 2)

LU

-

DC bus

undervoltage

Mains voltage too low

Check mains voltage

Voltage in DC-bus connection

too low

Check power supply module