Fault detection and elimination

Malfunction of the drive

U

EDK82MV222 DE/EN/FR 9.0

NPN

L

Fault

Cause

Remedy

Motor does not rotate

DC-bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display

LU

)

Check mains voltage

Controller inhibited
(Green LED is blinking, keypad display:
)

Remove the controller inhibit,

controller inhibit can be set

through several sources

Automatic start inhibited

(C0142 = 0 or 2)

LOW-HIGH edge at X3/28
If necessary, correct start

condition (C0142)

DC injection brake (DCB) active

Deactivate DC injection brake

Mechanical motor brake is not released Manual or electrical release of

mechanical motor brake

Quick stop (QSP) active (keypad display:
)

Remove quick stop

Setpoint = 0

Select setpoint

JOG setpoint activated and JOG

frequency = 0

Select JOG setpoint

(C0037 ... C0039)

Active fault

Eliminate fault

Wrong parameter set active

Change to correct parameter

set via terminal

Operating mode C0014 = -4-, -5-, but

no motor parameter identification

executed

Motor parameter identification

(C0148)

Under C0410 several functions which

exclude each other, are assigned to the

same signal source.

Correct configuration in C0410

Use of internal voltage source X3/20 for

function modules Standard I/O,

INTERBUS, PROFIBUS-DP or LECOM-B

(RS485):
Jumper between X3/7 and X3/39 is

missing

Jumper terminals

Motor does not rotate smoothly

Defective motor cable

Check motor cable

Maximum current set too low (C0022,

C0023)

Adapt settings to the

application

Motor underexcited or overexcited

Check parameter setting

(C0015, C0016, C0014)

C0084, C0087, C0088, C0089, C0090,

C0091 and/or C0092 are not adapted to

the motor data

Manual adaptation or

identification of motor

parameters (C0148)

Current consumption of motor

too high

Setting of C0016 too high

Correct setting

Setting of C0015 too low

Correct setting

C0084, C0087, C0088, C0089, C0090,

C0091 and/or C0092 are not adapted to

the motor data

Manual adaptation or

identification of motor

parameters (C0148)

Motor rotates, setpoints are “0”

With the function  of the keypad a

setpoint has been selected.

Set the setpoint to ”0” via

C0140 = 0