Commissioning

The most important codes for commissioning

T

EDK82MV222 DE/EN/FR 9.0

NOT

L

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0034*

uSEr

Setpoint

selection

range
Standard–I/O

(X3/8)

-12-

Observe the switch position

of the function module!

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10

V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Changing the direction of

rotation is only possible with

a digital signal.

2

Bipolar voltage -10 V ... +10 V

z

Minimum output

frequency (C0010) not

effective

z

Individual adjustment of

offset and gain

3

Current 4 ... 20 mA open-circuit

monitored

TRIP Sd5, if I < 4 mA
Changing the direction of

rotation is only possible with

a digital signal.

C0034*

(A)

uSEr

Setpoint

selection

range
Application I/O

Observe the jumper setting of

the function module!

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10

V

2 X3/2U, X3/2I

1

Bipolar voltage -10 V ... +10 V

Minimum output frequency

(C0010) not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Changing the direction of

rotation is only possible with

a digital signal.

4

Current 4 ... 20 mA open-circuit

monitored

Changing the direction of

rotation is only possible with

a digital signal.
TRIP Sd5 if I < 4 mA

C0037

JOG1

20.00 -650.00

{0.02

Hz}

650.00 JOG = fixed setpoint

Additional fixed setpoints

Ö

C0440

C0038

JOG2

30.00 -650.00

{0.02

Hz}

650.00

C0039

JOG3

40.00 -650.00

{0.02

Hz}

650.00

C0050*

uSEr

Output

frequency

(MCTRL1-NOU

T)

-650.00

{Hz}

650.00 Only display: Output

frequency without slip

compensation

C0087

Rated motor

speed

Æ

300

{1 rpm}

16000

Æ

Depending on the controller