Fault detection and elimination, Fault messages – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 136

Advertising
background image

U

Fault detection and elimination

Fault messages

EDK82MV222 DE/EN/FR 9.0

L

NPS

Remedy

Cause

Fault

PC

1)

Keypad

400 V controller is connected

to 240 V mains

Connect controller to correct

mains voltage

OC1

11

Short circuit

Short circuit

z

Search for cause of short

circuit; check motor cable

z

Check brake resistor and cable

to brake resistor

Capacitive charging current of

the motor cable too high

Use shorter/low-capacitance

motor cable

OC2

12

Earth fault

A motor phase has earth

contact

Check motor; check motor cable

Capacitive charging current of

the motor cable too high

Use shorter/low-capacitance

motor cable

Deactivate earth-fault detection

for inspection purposes

OC3

13

Controller

overload during

acceleration or

short circuit

Acceleration time set is too

short (C0012)

z

Increase acceleration time

z

Check drive dimensioning

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

14

Controller

overload during

deceleration

Deceleration time set is too

short (C0013)

z

Increase deceleration time

z

Check dimensioning of the

external brake resistor

OC5

15

Controller

overload during

steady-state

operation

Frequent and too long

overload

Check drive dimensioning

OC6

16

Motor overload

(I

2

x t overload)

Motor is thermally overload by

e.g.

z

impermissible continuous

current

z

Check drive dimensioning

z

frequent or too long

acceleration processes

z

Check setting of C0120

OH

50

Heatsink

temperature

> +85 °C

Ambient temperature is too

high

Allow controller to cool and

provide better ventilation

OH

-

Heatsink

temperature

> +80 °C

Heatsink is very dirty

Clean heatsink

Impermissibly high currents or

frequent and too long

acceleration processes

z

Check drive dimensioning

z

Check load, exchange

rough-running, defective

bearings if necessary

OH3

53

PTC monitoring

(TRIP)
(Display when

C0119 = 1 or 4)

Motor too hot due to

impermissibly high currents or

frequent and too long

acceleration processes

Check drive dimensioning

Advertising