Commissioning, The most important codes for commissioning – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 126

Advertising
background image

T

Commissioning

The most important codes for commissioning

EDK82MV222 DE/EN/FR 9.0

L

NOS

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0013

uSEr

Deceleration

time main

setpoint

5.00 0.00

{0.02

s}

1300.00 Reference: frequency change

C0011 ... 0 Hz

z

Additional setpoint

Ö

C0221

z

Deceleration times can be

activated via digital
signals

Ö

C0103

C0014

Operating

mode

2

2

V/f characteristic control V ~ f
(Linear characteristic with constant

V

min

boost)

z

Commissioning without

motor parameter

identification possible

z

Benefit of identification

with C0148:
– Improved smooth

running at low speed

– V/f rated frequency

(C0015) and slip

(C0021) are calculated

and stored. They do not

have to be entered

3

V/f characteristic control V ~ f

2

(Square-law characteristic with

constant V

min

boost)

4

Vector control

For initial selection enter

the motor data and identify

the motor parameters with

C0148
Otherwise commissioning

is not possible

5

Sensorless torque control with

speed limitation

z

Torque setpoint via C0412/6

z

Speed limitation via setpoint 1

(NSET1-N1), if C0412/1 is

assigned, if not via max.

frequency (C0011)

C0015

uSEr

V/f rated

frequency

50.00 7.50

{0.02

Hz}

960.00

z

C0015 is calculated and

stored under C0148 when

the motor parameters are

identified

z

Settings applies to all

mains voltages permitted

C0016

uSEr

V

min

boost

Ж

0.00

{0.01

%}

40.00

Ж

Depending on the controller

Setting applies to all mains

voltages permitted