Commissioning, The most important codes for commissioning – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 128

Advertising
background image

T

Commissioning

The most important codes for commissioning

EDK82MV222 DE/EN/FR 9.0

L

NOU

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0088

Rated motor

current

Æ

0.0

{0.1 A}

650.0

Æ

Depending on the controller

0.0 ... 2.0 x rated output

current of the controller

C0089

Rated motor

frequency

50

10

{1 Hz}

960

C0090

Rated motor

voltage

Æ

50

{1 V}

500

Æ

230 V with 230 V

controllers,

400 V with 400 V

controllers

C0091

Motor cos ϕ

Ж

0.40

{0.1}

1.0

Ж

Depending on the controller

C0119

-13-

Configuration

of motor

temperature

monitoring

(PTC input) /

earth fault

detection

0

0

PTC input not

active

Earth fault

detection active

z

Signal output

configuration under

C0415

z

If several parameter sets

are used, the monitoring

must be separately

adjusted for each

parameter set.

z

Deactivate the earth fault

detection, if it has been

activated unintentionally.

z

If the earth fault detection

is active, the motor starts

after controller enable

with a delay of approx.40

ms.

1

PTC input

active,
TRIP set

2

PTC input

active,
Warning set

3

PTC input not

active

Earth fault

detection

inactive

4

PTC input

active,
TRIP set

5

PTC input

active,
Warning set

C0140* Additive

frequency

setpoint

(NSET1-NADD)

0.00 -650.00

{0.02

Hz}

650.00

z

Selection via function
 of the keypad or the

parameter channel

z

Is added to main setpoint

z

Value is stored when

switching the mains or

removing the keypad