Wall mounting

Wiring according to EMC requirements

P

EDK82MV222 DE/EN/FR 9.0

VR

L

`зеЗбнбзел Сзк íêçìÄäÉJÑêÉÉ зйЙк~íáçåW

z

bñÅÉéí Сзк нЬЙ г~бел Е~ÄäÉI млЙ лЬбЙдЗЙЗ Е~ДдЙл çåäóK

z

qЬЙ лЬбЙдЗ гмлн ДЙ Е~кЙСмдду ЕзееЙЕнЙЗ нз mbK

z

pЙй~к~нЙ Езенкзд ~еЗ г~бел Е~ДдЙл Скзг гзнзк Е~ДдЙ>

z

`зееЙЕн гзнзк ~еЗ г~бел mb ЕзеЗмЕнзкл нз лЙй~к~нЙ mb нЙкгбе~длK

^

`

c

_

b

f

uN

8200mot100

g

cáÖK S

d

e

a

uO

Shield connection
1. Prepare cable

2. Route the cable through

the eyebolt of the shield

and bend the eyebolt.

3. Tighten the screw. The

shield must be tightly

connected to the shield

sheet.

0.7 Nm

6 lb-in

PES

Mains cable L1, L2, L3, PE

PE connection - mains cable

Use shielded motor cable (use low capacity motor cables)

EMC cable connection for motor cables

PE connection - motor cable

Shielded control cable

Shield connection for control cable (screw shield to shield sheet)

PE connection - terminal strip X2

Isolated terminal (e.g. star point for motor star connection)

Function module

X1

Terminal strip - mains connection

X2

Terminal strip - motor connection

PES

HF shield connection by connecting the shield with a surface as large as possible to PE