Commissioning, Vector control, Z y w x – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 115

Advertising
background image

Commissioning

Vector control

T

EDK82MV222 DE/EN/FR 9.0

NNR

L

12.

Activate the control mode ”vector

control” (C0014 = 4)
Lenze setting: Linear V/f

characteristic control (C0014 =

2)

E82ZBC014

z
y

w x

v

t

u

s

4

00 14

000

1

c

d

f

PS

Œ

p

Para

H/L

Subcode

Disp

Set

13.

Adapt the voltage/current range

for the analog setpoint selection

(C0034)
Lenze setting: -0-,

(0 ... 5 V/0 ... 10 V/0 ... 20 mA)

z
y

w x

0

000

a

b

c

d

e

‚m n o

p

q r

Hi
Lo

1

j g f k i h PS

Œ

0034

Set the DIP switch on the

standard I/O to the same

range (see Mounting

Instructions for the

standard I/O)

14.

Enter the motor data

See motor nameplate

A Rated motor speed (C0087)

Lenze setting: 1390 rpm

B Rated motor current (C0088)

Lenze setting: Depends on the

controller

Enter the value for the

motor connection type

(star/delta) selected!

C Rated motor frequency (C0089)

Lenze setting: 50 Hz

D Rated motor voltage (C0090)

Lenze setting: Depends on the

controller

Enter the value for the

motor connection type

(star/delta) selected!

E Motor-cosϕ (C0091)

Lenze setting: Depends on the

controller