Commissioning, Vector control – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 116

Advertising
background image

T

Commissioning

Vector control

EDK82MV222 DE/EN/FR 9.0

L

NNS

15.

Start the motor parameter

identification (C0148)

Only when the motor is

cold!

A Ensure that the controller is

inhibited

misc001

20

28

X3

}

Terminal X3/28 = LOW

B Set C0148 = 1

Press 

C Enable the controller

misc002

20

28

X3

z

Terminal X3/28 =

HIGH

z

The identification

starts:
– The segment 

is off

– The motor

consumes current

and makes a

“high-pitched”

tone.

– The motor does not

rotate!

D If the segment  becomes

active after approx. 30 s, inhibit

the controller once again.

misc001

20

28

X3

}

z

Terminal X3/28 =

LOW

z

Identification is

completed.

z

Calculated and

stored:
– V/f rated frequency

(C0015)

– Slip compensation

(C0021)

– Motor stator

inductance (C0092)

z

Measured and stored:
– Motor stator

resistance (C0084)

= Total resistance

of motor cable and

motor

Advertising