Commissioning, Vector control – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual
Page 116
T
Commissioning
Vector control
EDK82MV222 DE/EN/FR 9.0
L
NNS
15.
Start the motor parameter
identification (C0148)
Only when the motor is
cold!
A Ensure that the controller is
inhibited
misc001
20
28
X3
}
Terminal X3/28 = LOW
B Set C0148 = 1
Press
C Enable the controller
misc002
20
28
X3
z
Terminal X3/28 =
HIGH
z
The identification
starts:
– The segment
is off
– The motor
consumes current
and makes a
“high-pitched”
tone.
– The motor does not
rotate!
D If the segment becomes
active after approx. 30 s, inhibit
the controller once again.
misc001
20
28
X3
}
z
Terminal X3/28 =
LOW
z
Identification is
completed.
z
Calculated and
stored:
– V/f rated frequency
(C0015)
– Slip compensation
(C0021)
– Motor stator
inductance (C0092)
z
Measured and stored:
– Motor stator
resistance (C0084)
= Total resistance
of motor cable and
motor