Drive different loads with the 1756-of8i module, Wire the 1756-of8i module – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 5

1756-OF8I Isolated Analog Output Module

Drive Different Loads
with the 1756-OF8I Module

When the 1756-OF8I module operates with a Current output load, each channel
automatically adjusts its output power for 0…1000 ohm loads. The module’s 24V
backplane current requirements vary based on load.

For more information the module’s 24V current requirements, see the 1756
ControlLogix I/O Specifications Technical Data, publication

1756-TD002

.

Wire the 1756-OF8I Module

The following graphic show wiring examples for the 1756-OF8I module with
current and voltage output types.

Figure 23 - 1756-OF8I Module Wiring Diagram - Current Output Type

1
3
5

7

0

1

9

11

12

4

1

3

1

6

1

5

1

8

1

7

1

0

2

9

1

2

2

1

2

4

2

3

2

6

2

5

2

8

2

7

2

0

3

9

2

2

3

1

3

33

6

3

5

3

2

34

8

6

4

i

OUT_0/V

OUT_0/I

RTN_0

Not used

OUT_2/V

OUT_2/I

RTN_2

Not used

< 1000 Ω User
Analog Output

Device

OUT_4/V

OUT_4/I

RTN_4

Not used

OUT_6/V

OUT_6/I

RTN_6

Not used

Not used

Not used

OUT_1/V

OUT_1/I

RTN_1

Not used

OUT_3/V

OUT_3/I

RTN_3

Not used

OUT_5/V

OUT_5/I

RTN_5

Not used

OUT_7/V

OUT_7/I

RTN_7

Not used

Not used

Not used

IMPORTANT: Remember the following:
If separate power sources are used, do

not exceed the specific isolation
voltage. For more information on
module specifications, see the 1756
ControlLogix I/O Specifications
Technical Data, publication

1756-TD002

.

Place additional devices anywhere in

the loop.