Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

121

Chapter

7

Configure ControlLogix Isolated Analog
I/O Modules

You must configure your isolated analog I/O module upon installation. It does
not work if it is not configured.

This section describes how to use the Logix Designer application to configure
I/O modules in a local chassis. If you plan to use the I/O module in a remote
chassis, you must add a ControlNet or EtherNet/IP communication module to
the I/O configuration tree:

For more information on the ControlLogix ControlNet module, see
ControlNet Modules in Logix5000 Control Systems,
publication

CNET-UM001

.

For more information on the ControlLogix EtherNet/IP Bridge module,
see EtherNet/IP Modules in Logix5000 Control Systems User Manual,
publication

ENET-UM001

.

Topic

Page

Create a New Module

122

Edit the Configuration

125

Copy Channel Configuration

134

View the Module Tags

136

IMPORTANT

This chapter describes how to configure you module with Logix Designer
application, version 21 and later.

You can use the ControlLogix isolated analog I/O modules in RSLogix 5000
software projects as well.

You must install AOPs to use the modules in any Logix Designer application
or RSLogix 5000 software project.