Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

159

Troubleshoot Your Module

Chapter 9

Status Indicators for the
1756-OF8I Module

The following graphic shows the status indicators used with 1756-OF8I module.

The following table describes the status indicators.

ANALOG OUPUT

ST

FLT

O

K

Indicator

Status

Description

OK

Steady green

The module is in a normal operating state in Run mode.

Flashing green

The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.

Flashing red

Previously established communication has timed out.

Steady red

Replace the module.

ST

Steady yellow

The channel is operating as expected.

Flashing yellow

The channel is being calibrated.

Off

The channel is not in use or is faulted.

FLT

Off

The channel is operating as expected.

Steady red

The channel is faulted. Some possible causes of the fault include:

Triggered clamp alarm
Wire off detection
Calibration fault

For more information on these causes see Chapter 5,

1756-OF8I Isolated

Analog Output Module on page 93

Flashing red

The channel is faulted. See the previous row for more information
about faults.