Output tags – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 196

Advertising
background image

196

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Appendix A

Isolated Analog I/O Module Tag Definitions

Output Tags

The following table describes the Output tags associated with the
1756-OF8I module.

Table 28 - 1756-OF8I Module - Output Tags

Tag Name

Size

Definition

Valid Values

Ch[x].LLimitUnlatch

BOOL

Unlatches a latched Low Limit alarm at the first instance
of the bit transitioning from 0 to 1.
For example, if the controller sends data for this tag in
successive instances as 0, 1, 1, 1, 1, the module unlatches
the Low Limit alarm when it receives the first 1.
The following instances of this tag value being 1 do not
impact the Low Limit alarm unlatching.

0 = Alarm remains latched

(default)

1 = Alarm is unlatched

Ch[x].HLimitUnlatch

BOOL

Unlatches a latched High Limit alarm at the first instance
of the bit transitioning from 0 to 1.
For example, if the controller sends data for this tag in
successive instances as 0, 1, 1, 1, 1, the module unlatches
the High Limit alarm when it receives the first 1.
The following instances of this tag value being 1 do not
impact the High Limit alarm unlatching.

0 = Alarm remains latched

(default)

1 = Alarm is unlatched

Ch[x].RampAlarmUnlatch

BOOL

Unlatches a latched Ramp alarm at the first instance of
the bit transitioning from 0 to 1.
For example, if the controller sends data for this tag in
successive instances as 0, 1, 1, 1, 1, the module unlatches
the Ramp alarm when it receives the first 1.
The following instances of this tag value being 1 do not
impact the Ramp alarm unlatching.

0 = Alarm remains latched

(default)

1 = Alarm is unlatched

Ch[x].Calibrate

BOOL

Initiates the Calibration process.
This tag must remain set until a valid Low Reference and
High Reference values are applied to the channel.

0 = Calibration process is

not started (default)

1 = Calibration process is started

Ch[x].CalOutputLowRef

BOOL

Data value change that transitions the channel to produce
the Low Calibration Reference Point for the current
C.Ch[x].OutputRange tag value.

0 = Do not output Cal Low

Reference

1 = Output Calibration Low

Reference

Do not set his tag and the
CalOutputHighRef tag to 1
simultaneously.