Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 166

Advertising
background image

166

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 9

Troubleshoot Your Module

If the previously listed tasks fail to resolve your issue with incorrect RTD readings
on your module, use the following table.

Table 17 - 1756-IRT8I Module - Troubleshoot Incorrect RTD Readings

Possible Cause of Incorrect
Reading

Description

Recommended Action

Wire Off

When using a 3-wire RTD
device and any of the following:

One wire is disconnected

from any of the channel’s
terminals.

Wires are disconnected from

any combination of
terminals:
IN_x(+)/A
IN_x(-)/B
IN_x/RTD C

All of the wires are

disconnected from the
channel.

The following occurs:

Input data for the channel

changes to the highest scaled
temperature value associated
with the selected sensor type.

The I.Ch[x].Overrange tag is

set to 1.
x represents the channel
number.

Check the wiring, terminations, and for an open wire.

Make sure the length of the RTD cable is within module

specifications.
Wire length that is too long has a higher impedance, and can be
interpreted as an open circuit.

When using a 4-wire RTD
device and any of the following:

A wire is disconnected from

only terminal IN_x(-)/B.

Wires are disconnected from

any combination of the
channel’s terminals, that is:
IN_x(+)/A
IN_x(-)/B
IN_x/RTD C
IN_x/RTD D
IMPORTANT: There is one
combination exception that
does not apply.

A wire off condition is not
detected when wires are
simultaneously disconnected
from only IN_x/RTD C and
IN_x/RTD D terminals.

All wires are disconnected

from the module.

If bullet 1, the following occurs:

Input data for the channel

changes to the lowest scaled
temperature value associated
with the selected sensor type.

The I.Ch[x].Underrange tag is

set to 1.
x represents the channel
number.

If bullets 2 or 3, the following
occurs:

Input data for the channel

changes to the highest scaled
temperature value associated
with the selected sensor type.

The I.Ch[x].Overrange tag is

set to 1.
x represents the channel
number.

Advertising