Calibration, Calibrated accuracy, Calibrated accuracy at 25 °c (77 °f) – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 38: Calibration calibrated accuracy

Advertising
background image

38

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 2

ControlLogix Isolated Analog I/O Module Features

Calibration

The ControlLogix isolated analog modules are calibrated via the
following methods:

Factory calibration when the modules are built.

User-executed calibration as described in

Chapter 8

,

Calibrate the

ControlLogix Isolated Analog I/O Modules on page 137

.

User-executed calibration is optional.

• 1756-IRT8I module only

- Channels configured for Thermocouple

inputs perform a lead resistance self-calibration when the module power
is cycled.

Calibrated Accuracy

The Calibrated Accuracy specification represents the module’s accuracy when
its ambient temperature is the same as the temperature at which the module
was calibrated.

The following specifications are related to Calibrated Accuracy:

Calibrated Accuracy at 25 °C (77 °F)

Module Error over Full Temperature Range

Calibrated Accuracy at 25 °C (77 °F)

This specification matches the temperature at which the module was calibrated
in the factory during manufacturing.

The module’s accuracy when operating in 25 °C (77 °F) conditions = 0.05%.