9 - troubleshoot your module, Status indicators for the 1756-if8i module, Chapter 9 – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 157: Troubleshoot your module, Chapter

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
157
Chapter
9
Troubleshoot Your Module
ControlLogix isolated analog I/O module have status indicators on the front of
the module that are used to monitor module operation.
Status Indicators for the
1756-IF8I Module
The following graphic shows the status indicators used with 1756-IF8I modules.
The following table describes the status indicators.
Topic
Page
Status Indicators for the 1756-IF8I Module
Status Indicators for the 1756-IRT8I Module
Status Indicators for the 1756-OF8I Module
Use Logix Designer Application for Troubleshooting
Troubleshoot Incorrect Readings on the Module
Indicator
Status
Description
OK
Steady green
The module is in a normal operating state in Run mode.
Flashing green
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Flashing red
Previously established communication has timed out.
Steady red
Replace the module.
ST
Steady yellow
The channel is operating as expected.
Flashing yellow
The channel is being calibrated.
Off
The channel is not in use or is faulted.