Page 36

Advertising
background image

36

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 2

ControlLogix Isolated Analog I/O Module Features

The following table lists the resolution for each module’s input/output range and
corresponding range capability.

Table 2 - Module Resolution in Various Configuration Selections

Module

Mode

Available Input/
Output Range

(1)

Actual Input/Output
Range Capability

Number of Bits
Across the
Theoretical
Operating Range

Number of Bits
Across the Actual
Range Capability

Resolution (signal
per count)

1756-IF8I

Voltage

-10…10V
0…10V
0…5V

-10.5…10.5V
0…10.5V
0…5.25V

24 bits

23.75
22.75
21.75

1.49 μV/count

Current

0…20 mA
0…20 mA (sourcing)

0…21 mA
0…21 mA (sourcing)

22.74

2.99 nA/count

1756-IRT8I

Thermocouple

-100…100 mV

-101…101 mV

24 bits

23.98

0.01 μV/count

RTD

1…500

Ω

2…1000

Ω

4…2000

Ω

8…4000

Ω

0…510

Ω

0…1020

Ω

0…2040

Ω

0…4080

Ω

23.98

0.06 m

Ω

/count

0.12 m

Ω

/count

0.25 m

Ω

/count

0.50 m

Ω

/count

1756-OF8I

Voltage

-10…10V
0…10V
0…5V

-10.5…10.5V
0…10.5V
0…5.25V

16 bits

16.00

0.32 mV/count
0.16 mV/count
0.08 mV/count

Current

0…20 mA

0…21 mA

16.00

0.32 μA

(1) These ranges represent the range choices available in the Logix Designer application.

IMPORTANT

Because these modules must allow for possible calibration inaccuracies,
resolution values represent the available Analog-to-Digital or Digital-to-
Analog counts over the specified range.

Additionally, RPI and Notch Filter settings affect module resolution on the
1756-IF8I and 1756-IRT8I modules. For more information, see

page 49

and

page 68

, respectively.