Chapter 8

Calibrate the ControlLogix Isolated Analog I/O Modules

Calibrate the 1756-IF8I Module For Voltage Input Type

During voltage calibration, 0.0V and +10.0V external references are applied to
the module’s channels. The module records the deviation from these reference
values and stores it as calibration constants in the module’s firmware.

The internal calibration constants are then used in every subsequent signal
conversion to compensate for circuit inaccuracies, including the input amplifier,
resistors, and the A/D convertor.

The 1756-IF8I offers three input voltage ranges:

-10…10V

0…5V

0…10V

Follow these steps to calibrate your 1756-IF8I module.

1.

Connect your voltage calibrator to all module channels being calibrated.

2.

Go online with your project.

3.

Right-click the module you want to calibrate and choose Properties.

IMPORTANT

Regardless of the input voltage range selected prior to calibration, all
voltage calibration uses the -10…10V range.