1756-if8i module tags, Configuration tags – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 175

Advertising
background image

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

175

Isolated Analog I/O Module Tag Definitions

Appendix A

1756-IF8I Module Tags

This section describes the tags associated with the 1756-IF8I module.

Configuration Tags

The following table describes the Configuration tags associated with the
1756-IF8I module.

IMPORTANT

Each application’s series of tags varies but no input module application
contains any tags that are not listed here.

Table 20 - 1756-IF8I Module - Configuration Tags

Tag Name

Size

Definition

Valid Values

Ch[x].InputRange

SINT

Channel’s operating range.

0 = -10…10V
1 = 0…5V
2 = 0…10V
3 = 0…20 mA (default)

Ch[x].NotchFilter

SINT

Notch Filter removes line noise for the channel.
There is a relationship between this setting and the RPI
setting. For more information on Notch Filter, see

page 48

.

0 = 10 Hz
1 = 50 Hz
2 = 60 Hz (default)
3 = 100 Hz
5 = 1000 Hz
6 = 20 Hz
7 = 15 Hz
8 = 500 Hz
9 = 5000 Hz
10 = 5 Hz

Ch[x].AlarmDisable

BOOL

Disables all alarms on the module.

0 = Enabled

1 = Disabled (default)

Ch[x].ProcessAlarmLatch

BOOL

Latches all Process alarms if they are configured not to
clear until explicitly unlatched.

0 = Latching disabled (default)

1 = Latching enabled

Ch[x].RateAlarmLatch

BOOL

Latches all Rate Alarms when set so that they do not clear
until explicitly unlatched.

0 = Latching disabled (default)

1 = Latching enabled

Ch[x]. Disable

BOOL

Disables the channel.

0 = Enabled (default)

1 = Disabled

Ch[x].Sourcing

BOOL

When in current mode, indicates if channel is Sinking or
Sourcing.

0 = Sinking (default)

1 = Sourcing

Ch[x].SynchronizeSampling

BOOL

Determines if the sampling of the channel is synchronized
with other channels configured as synchronized.

0 = Not synchronized (default)

1 = Synchronized

Ch[x].DigitalFilter

INT

Time Constant for a First Order Lag filter.

0…32,767 ms
(0 = default)

Advertising