Isolated Analog I/O Module Tag Definitions

Appendix A

Ch[x].CalOutputHighRef

BOOL

Data value change that transitions the channel to produce
the High Calibration Reference Point for the current
C.Ch[x].OutputRange tag value.

0 = Do not Output Cal High

Reference

1 = Output Calibration High

Reference Signal

Do not set his tag and the
CalOutputLowRef tag to 1
simultaneously.

Ch[x].CalLowRefPassed

BOOL

Data value change that indicates that the O.Ch[x].Data tag
contains the recorded Low Reference value for the
channel that is used by the module in Calibration.

0 = Not sending Recorded Cal

Low Ref

1 = Sending Recorded Cal Low

Reference in Output Data for
Calibration Verification

Ch[x].CalHighRefPassed

BOOL

Data value change that indicates that the O.Ch[x].Data tag
contains the recorded High Reference value for the
channel that is used by the module in Calibration.

0 = Not sending Cal High

Reference

1 = Sending recorded

Calibration High Reference
Signal in Output Data for
Calibration Verification

Ch[x].CalFinishCalibration

BOOL

Data value change that triggers the channel to complete
the Calibration procedure, applying the Valid Low and
High References received.
Channel exits the Calibration state if successful.

0 = Channel not triggered to

complete the calibration
procedure

1 = Channel triggered to

complete the calibration
procedure

Ch[x].Data

REAL

Channel data in scaled Engineering Units.

Any positive or negative value.
Determined by how you set the
scaling parameters on the channel.
For more information, see

Scaling

on page 37

.

Table 28 - 1756-OF8I Module - Output Tags

Tag Name

Size

Definition

Valid Values