Input Tags

The following table describes the Input tags associated with the
1756-IRT8I module.

Table 24 - 1756-IRT8I Module - Input Tags

Tag Name

Size

Definition

Valid Values

Fault

DINT

Standard Analog Fault mask – controller sets all 32 bits on
connection loss.

0000_0000= Connection is

good

FFFF_FFFF Hex = Connection

has failed

CIPSyncValid

BOOL

Indicates whether the module has synchronized to a valid
CIP Sync time master on the backplane.

0 = CIP Sync is not available

1 = CIP Sync is available

CIPSyncTimeout

BOOL

Indicates whether a valid time master on the backplane
has timed out.

0 = A valid time master has not

timed out.

1 = A valid time master was

detected on the backplane, but
the time master has timed out.
The module is currently using its
local clock with old synchronized
time data.

CIPSyncOffsetJump

BOOL

Indicates a significant jump, that is, 1 ms or greater, in the
CST and CIP Sync times sent from the Timemaster to the
module. (The Timemaster sends the CST and CIP Sync
times to the module every second.)
When a significant jump occurs, this tag value becomes 1
but changes to 0 a second later unless another jump
occurred.
We recommend that you refresh the Diagnostic Assembly
to get more data on the jump if precise time tracking is
important to your application.

0 = No significant jump occurred

1 = Significant jump occurred

CJ[0].Underrange
CJ[1]Underrange

BOOL

The cold junction at channel x is below 0 °C.

0 = Cold junction is not below

0 °C

1 = Cold junction is below 0 °C

CJ[0].Overrange
CJ[1].Overrange

BOOL

The cold junction at channel x is above 86 °C.

0 = Cold junction is not above

86 °C

1 = Cold junction is above 86 °C

CJ[0].Data
CJ[1].Data

REAL

The cold junction at the top module terminal, that is,
CJ[0], or the bottom module terminal, that is, CJ[1] x
in Celsius.

Ch[x].Fault

BOOL

Quality of channel data.

0 = Good

1 = Bad

Ch[x].Uncertain

BOOL

Channel data can be imperfect.

0 = Good

1 = Uncertain