Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 80

Advertising
background image

80

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 4

1756-IRT8I Combined Temperature-sensing Isolated Analog Module

Thermocouple (mV)

TC Type B

21…1820 °C
68…3308 °F
293…2093 °K
528…3768 °R

TC Type C

0…2320 °C
32…4208 °F
273…2593 °K
492…4668 °R

TC Type D

0…2320 °C
32…4208 °F
273…2593 °K
492…4668 °R

TC Type E

-270…1000 °C
-454…1832 °F
3…1273 °K
6…2292 °R

TC Type J

-210…1200 °C
-346…2192 °F
63…1473 °K
114…2652 °R

TC Type K

-270…1372 °C
-454…2502 °F
3…1645 °K
6…2961 °R

TC Type N

-270…1300 °C
-454…2372 °F
3…1573 °K
6…2832 °R

TC Type R

-50…1768 °C
-58…3215 °F
223…2041 °K
402…3674 °R

TC Type S

-50…1768 °C
-58…3215 °F
223…2041 °K
402…3674 °R

TC Type T

-270…400 °C
-454…752 °F
3…673 °K
6…1212 °R

TC Type TXK/XK (L)

-200…800 °C
-328…1472 °F
73…1073 °K
132…1932 °R

Table 12 - Temperature Limits for RTD and Thermocouple Sensor Types

Input Type

Sensor Type

Temperature Range Limits

Advertising