Connect the grounded end of the cable – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 110

Advertising
background image

110

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 6

Install ControlLogix Isolated Analog I/O Modules

Connect the Grounded End of the Cable

Before wiring the RTB, you must connect the ground wiring.

1.

Remove a length of cable jacket from the Belden cable.

2.

Pull the foil shield and bare drain wire from the insulated wire.

3.

Twist the foil shield and drain wire together to form a single strand.

4.

Attach a ground lug and apply heat shrink tubing to the exit area.

IMPORTANT

We recommend that you ground the following ControlLogix isolated analog
module shield and drain wires at the field-side:

1756-OF8I

1756-IRT8I

1756-IF8I on points that use the non-sourcing current/voltage

functionality

If you cannot ground the module shield and drain wires at field-side, ground
them at an earth ground on the chassis.

We recommend that you always ground the 1756-IF8I module at an earth
ground on the chassis
when you use the module’s current sourcing
functionality
.

45077

45078

45079

45080