Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 155
Advertising

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
155
Calibrate the ControlLogix Isolated Analog I/O Modules
Chapter 8
The Output Reference Signals dialog box appears, as shown below. It
indicates the channels are calibrated for a high reference and the
calibration range.
12.
Click Next.
The Measure and Record Values dialog box appears.
13.
For each channel being calibrated, use your current meter to measure the
reference value of each channel individually.
14.
In the Recorded Reference (mA) column record the measured value for
each channel that was recorded and click Next.
Advertising