Chapter 4

1756-IRT8I Combined Temperature-sensing Isolated Analog Module

Cold Junction Offset Option

The Cold Junction Offset box on the Module Properties Configuration Tab lets
you make module-wide adjustments to cold junction compensation values. If you
know that your cold junction compensation values are consistently inaccurate by
some level, for example, 1.2 °C, type the value into the box to account for this
inaccuracy.

IMPORTANT

Consider the following before disabling cold junction compensation:

We recommend that you do not disable the cold junction disable option.

Typically, this option is used only in systems that have no thermoelectric
effect, such as test equipment in a controlled lab.

The Cold Junction Disable box on the Module Properties Configuration tab

disables cold junction compensation on all module channels.

IMPORTANT

Cold Junction temperatures are always reported as Celsius temperature units,
and, offset values are always set in Celsius temperature units.

You cannot change the temperature units.

Type offset value.