Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

193

Isolated Analog I/O Module Tag Definitions

Appendix A

Ch[x].FaultFinalState

REAL

Value to which the channel changes if the following
events exist:
Connection is lost
Time defined by the C.Ch[x].FaultValueStateDuration

tag has been exceeded

Any
0.0 = default

Ch[x].ProgValue

REAL

Value to which the channel changes if the following
events exist:
Module transitions to Program mode
C.Ch[x].ProgMode tag is enabled

Any
0.0 = default

Ch[x].LowSignal

REAL

Signal value that lets you scale signal units (V, mA) into
Engineering Units.
Corresponds to the C.Ch[x].LowEngineering tag. That is,
this tag’s value is scaled to the lowest Engineering Unit.

Any value less the
C.Ch[x].HighSignal tag value.
Current input type: 4.0 = default
Voltage input type: -10.0 = default

Ch[x].HighSignal

REAL

Signal scaling value that lets you scale signal units (V, mA)
into Engineering Units.
Corresponds to the C.Ch[x].HighEngineering tag. That is,
this tag’s value is scaled to the highest Engineering Unit.

Any value greater than the
C.Ch[x].LowSignal tag value
Current input type: 20.0 = default
Voltage input type: 10.0 = default

Ch[x].LowEngineering

REAL

Low engineering scaling point
Corresponds to the C.Ch[x].LowSignal tag value.

Any lower than the
C.Ch[x].HighEngineering tag
Default values:
0.0 for current
-10.0 for voltage

Ch[x].HighEngineering

REAL

High engineering scaling point
Corresponds to the C.Ch[x].HighSignal tag value.

Any higher than the
C.Ch[x].LowEngineering tag
Default values:
100.0 for current
10.0 for voltage

Ch[x].LowLimit

REAL

LowLimit setpoint below which the output cannot go
when Clamping is enabled.

Any lower than the HighLimit
0.0 = default

Ch[x].HighLimit

REAL

HighLimit setpoint above which the output cannot go
when Clamping is enabled.

Any higher than the LowLimit
0.0 = default

Ch[x].Offset

REAL

Compensates for any known error on the sensor or
channel to which the sensor is connected. The value is set
in signal units.

Any
(We recommend that you use a
small value.)
0.0 = default

Table 26 - 1756-OF8I Module - Configuration Tags

Tag Name

Size

Definition

Valid Values