Calibrate in program mode, Calibrate the input modules, Calibrate the 1756-if8i module – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 139

Advertising
background image

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

139

Calibrate the ControlLogix Isolated Analog I/O Modules

Chapter 8

Calibrate in Program Mode

Your project must be online with the controller to calibrate ControlLogix
isolated analog I/O modules. You can calibrate in the following conditions:

The controller in Program mode--either Remote Program or Program
mode.

We recommend that your module be in Program mode and not be actively
controlling a process when you calibrate it.

The controller in Run mode-either Remote Run or Run mode.

In this case, you must inhibit the connection from the controller to the
module being calibrated before beginning the calibration process.

Calibrate the Input Modules

Input calibration is a multi-step process. You apply low and high signal references
to the module at different steps in the process.

Calibrate the 1756-IF8I Module

You can calibrate the 1756-IF8I module for use with the following input types:

Current (mA)

Voltage (V)

IMPORTANT

The module freezes the state of each channel and does not update the
controller with new data until after the calibration ends. This could be
hazardous if active control were attempted during calibration.

Topic

Page

Calibrate the 1756-IF8I Module

139

Calibrate the 1756-IRT8I Module

144

IMPORTANT

This section shows how to calibrate the 1756-IF8I modules for use with only
voltage inputs.

The calibration process is generally the same if you calibrate the module for use
with current inputs except for the following differences:

You connect a current calibrator to the module.

The low reference signal applied to the module = 4 mA.

The high reference signal applied to the module = 20 mA.