1756-IRT8I Combined Temperature-sensing Isolated Analog Module

Chapter 4

The following table lists temperature range limits on the 1756-IRT8I module.

Table 12 - Temperature Limits for RTD and Thermocouple Sensor Types

Input Type

Sensor Type

Temperature Range Limits

RTD (Ohms) - 3-wire or 4-wire 100 Ohm PT 385

200 Ohm PT 385
500 Ohm PT 385
1000 Ohm PT 385

-200…870 °C
-328…1598 °F
73…1143 °K
132…2058 °R

100 Ohm PT 3916
20 Ohm PT 3916
500 Ohm PT 3916
1000 Ohm PT 3916

-200…630 °C
-328…1166 °F
73…903 °K
132…1626 °R

10 Ohm CU 247

-200…260 °C
-328…500 °F
73…533 °K
132…960 °R

120 Ohm NI 672

-80…320 °C
-112…608 °F
193…593 °K
348…1068 °R

100 Ohm NI 618
120 Ohm NI 618
200 Ohm NI 618
500 Ohm NI 618

-60…250 °C
-76…482 °F
213…523 °K
384…942 °R