Isolated Analog I/O Module Tag Definitions

Ch[x].RateAlarmUnlatch

BOOL

Unlatches a latched Rate Alarm at the first instance of the
bit transitioning from 0 to 1.
For example, if the controller sends data for this tag in
successive instances as 0, 1, 1, 1, 1, the module unlatches
the Process alarm when it receives the first 1.
The following instances of this tag value being 1 do not
impact the Process alarm unlatching.

0 = Rate Alarm remains latched

1 = Rate Alarm unlatches

Ch[x].Calibrate

BOOL

Initiates the Calibration process.
This tag must remain set until a valid Low Reference and
High Reference values are applied to the channel.

0 = Calibration process is

not started

1 = Calibration process is started

Ch[x].CalLowReference

BOOL

Rising edge triggers the Low Calibration at the Low
Reference Point for the current InputRange tag value.
A valid Low Reference signal must be connected to the
channel before setting this tag.

0 = Channel data value has not

passed the Low Reference Point
value

1 = Channel data value has

passed the Low Reference Point
value

Ch[x].CalHighReference

BOOL

Rising edge triggers a High Calibration at the High
Reference Point for the current InputRange tag value.
A valid High Reference signal must be connected to the
channel before setting tag.

0 = Channel data value has not

passed the High Reference Point
for the current InputRange tag
value

1 = Channel data value has

passed the High Reference Point
for the current InputRange tag
value

Ch[x].SensorOffset

REAL

Compensates for any known error on the sensor or
channel to which the sensor is connected.

Any
(We recommend that you use a
value in the channel’s operating
range.)
0.0 = default

Table 25 - 1756-IRT8I Module - Output Tags

Tag Name

Size

Definition

Valid Values