Chapter 8

Calibrate the ControlLogix Isolated Analog I/O Modules

The Attach Low Reference Voltage Signals dialog box appears, as shown
below. It indicates the channels are calibrated for a low reference and the
range of the calibration.

8.

Set the calibrator for the low reference and apply it to the module.

9.

Click Next.

The Group Low Reference Results dialog box indicates the status of each
channel after calibrating for a low reference.

10.

If channels are OK, click Next.

If any channel reports an error, return to

step 8

and click Retry until the

status is OK.

If the error persists indefinitely, click Stop to exit calibration. The channel
remains calibrated to the accuracy level achieved at factory calibration.