ControlLogix Isolated Analog I/O Module Features

Module Error at 25 °C (77 °F)

Table 4

lists the 1756-IRT8I module error at 25 °C (77 °F) when using a

thermocouple input type.

Table 4 - 1756-IRT8I Module Error At 25 °C (77 °F) with Thermocouple Input Type

Application
Temperature

Module Error at 25 °C (77 °F) When Connected to Thermocouple Types

Type B

Type C

Type D

Type TXK/
XK(L)

Type R

Type S

Type E

Type J

Type K

Type N

Type T

-200 °C (-328 °F)

1.65

1.79

2.06

2.95

4.53

2.86

0 °C (32 °F)

3.46

4.59

0.93

8.51

8.33

0.77

0.89

1.14

1.72

1.16

200 °C (392 °F)

2.65

2.83

0.71

5.09

5.32

0.61

0.81

1.13

1.36

0.85

400 °C (752 °F)

11.08

2.37

2.36

0.62

4.34

4.70

0.56

0.82

1.07

1.21

0.73

600 °C (1112 °F)

7.56

2.37

2.22

0.56

3.96

4.41

0.56

0.77

1.06

1.16

800 °C (1472 °F)

5.89

2.37

2.20

0.51

3.65

4.14

0.57

0.70

1.10

1.15

1000 °C (1832 °F)

4.93

2.37

2.25

3.40

3.90

0.60

0.76

1.15

1.17

1200 °C (2192 °F)

4.35

2.65

2.36

3.23

3.74

0.79

1.23

1.21

1400 °C (2552 °F)

3.99

2.81

2.47

3.18

3.71

1.33

1600 °C (2912 °F)

3.85

3.00

2.63

3.24

3.80

1800 °C (3272 °F)

3.92

3.46

2.85

3.67

4.36

2000 °C (3632 °F)

3.75

3.19

2200 °C (3992 °F)

4.09

3.95

IMPORTANT

When calculating total measurement error, module error at 25 °C (77 °F) is only
one factor in deriving the total measurement error budget.

Other factors that impact thermocouple measurement error include
the following:

Thermocouple sensor accuracy/error

Conditions of thermocouple wire, such as wire length

Cold junction compensation values