Status indicators for the 1756-irt8i module – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 158

Advertising
background image

158

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 9

Troubleshoot Your Module

Status Indicators for the
1756-IRT8I Module

The following graphic shows the status indicators used with
1756-IRT8I module.

The following table describes the status indicators.

FLT

Off

The channel is operating as expected.

Steady red

The channel is faulted.Possible causes of the fault include:

Underrange/overrange detection
Triggered process alarm
Triggered rate alarm
Wire off detection
Calibration fault

For more information on these causes see Chapter 3,

1756-IF8I Isolated

Analog Input Module on page 45

Flashing red

One of the following:

The channel is faulted. See the previous row for more information

about faults.

The channel is being calibrated.

RTD/TC/mV INPUT

ST

FLT

O

K

Indicator

Status

Description

OK

Steady green

The module is in a normal operating state in Run mode.

Flashing green

The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.

Flashing red

Previously established communication has timed out.

Steady red

Replace the module.

ST

Steady yellow

The channel is operating as expected.

Flashing yellow

The channel is being calibrated.

Off

The channel is not in use or is faulted.

FLT

Off

The channel is operating as expected.

Steady red

The channel is faulted. Some possible causes of the fault include:

Underrange/overrange detection
Wire off detection
Calibration fault

For more information on these causes see Chapter 4,

1756-IRT8I Combined

Temperature-sensing Isolated Analog Module on page 65

Flashing red

One of the following:

The channel is faulted. See the previous row for more information

about faults.

The channel is being calibrated.

Advertising