Calibrate the ControlLogix Isolated Analog I/O Modules

Chapter 8

11.

Set the calibrator for the high reference voltage and apply it to the module.

12.

Click Next.

The Group High Reference Results dialog box indicates the status of each
channel after calibrating for a high reference.

13.

If channels are OK, click Next.

If any channel reports an error, return to

step 11

and click Retry until the

status is OK.

If the error persists indefinitely, click Stop to exit calibration. The channel
remains calibrated to the accuracy level achieved at factory calibration.

14.

When the Calibration Completed dialog box appears, click Finish.