Chapter 8

Calibrate the ControlLogix Isolated Analog I/O Modules

Calibrate the 1756-IRT8I Module

You can calibrate the 1756-IRT8I module for use with the following input types:

RTD (Ohms) - 3 and 4 Wire types

Thermocouple (mV)

Calibrate the 1756-IRT8I Module for an RTD Input Type

The 1756-IRT8I uses two precision resistors to calibrate the channels in ohms.
You connect the following:

1

Ω

precision resistor for low reference calibration

487

Ω

precision resistor for high reference calibration

The 1756-IRT8I module can operate in multiple input ranges when an RTD is
connected. However, the module calibrates only in the 1…510

Ω

range.

Follow these steps to calibrate your module.

1.

Go online with your project.

2.

Right-click the module you want to calibrate and choose Properties.

IMPORTANT

After you connect either precision resistors, we recommend that you
wait for a minimum of two minutes before proceeding to the next task
to obtain the highest calibration accuracy.

For more information, see

page 146

and

page 147

.

IMPORTANT

When you are wiring precision resistors for calibration, follow the wiring
example on

page 89

. Make sure terminals IN_x(-)/B and IN_x/RTD C are

shorted together at the RTB.

You can calibrate the module for 3-wire or 4-wire mode. Calibrate in the
mode in which the module operates.