Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 2

ControlLogix Isolated Analog I/O Module Features

To see where to configure Electronic Keying, see

page 126

.

EXAMPLE

In the following scenario, Disable keying lets I/O
communication occur:

The module configuration is for a 1756-IA16 digital input module. The
physical module is a 1756-IB16 digital input module. In this case,
communication is allowed because the two digital modules share common
data formats.

IMPORTANT

Changing electronic keying selections online can cause the I/O
communication connection to the module to be disrupted and can result in

a loss of data.

Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1

Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2

Communication is allowed

ANALOG INPUT

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O
K

CAL

OK

OK

FORCE SD

RUN

Logix5575

RU

N REM PROG

DC INPUT

DC INPUT

FLT 8 9 10 11 12 13 14 15

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O
K

FLT 0 1 2 3 4 5 6 7

DIAGNOSTIC