Chapter

6

Install ControlLogix Isolated Analog I/O Modules

This chapter assumes that you have already installed a 1756 ControlLogix chassis
and power supply. If not, do so before proceeding.

Topic

Page

Install the I/O Module

106

Key the Removable Terminal Block

108

Connect Wiring

109

Assemble the RTB and the Housing

114

Choose Extended-depth Housing

115

Install the Removable Terminal Block

117

Remove the Removable Terminal Block

118

Remove the Module from the Chassis

119

ATTENTION: Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment,
in overvoltage Category II applications (as defined in EN 60664-1), at altitudes up
to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.

This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental conditions
that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-
retardant properties to prevent or minimize the spread of flame, complying with a
flame spread rating of 5VA or be approved for the application if nonmetallic. The
interior of the enclosure must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product safety
certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional installation requirements

NEMA 250 and EN 60529, as applicable, for explanations of the degrees of

protection provided by different types of enclosure