Direct connections – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 1

Isolated Analog I/O Module Operation in the ControlLogix System

• Remote chassis

- A chassis that does not contain the module’s owner-

controller but is connected to the local chassis over the EtherNet/IP
network or ControlNet network.

The Logix Designer application transfers configuration data to the controller
during the program download. Subsequently, data is transferred to the I/O
modules in the local and remote chassis.

The I/O module can operate immediately after the project download from the
owner-controller is complete.

Direct Connections

A direct connection is a real-time data transfer link between the controller and
the device that occupies the slot that the configuration references.

When you download module configuration to a controller, the controller
attempts to establish a direct connection to each module referenced by the
configuration.

OK

FORCE SD

RUN

Logix5575

RU

N REM PROG

ANALOG INPUT

ST

FLT

O

K

ST

FLT

O

K

ANALOG OUTPUT

ANALOG INPUT

ST

FLT

O

K

ST

FLT

O

K

ANALOG OUTPUT

ANALOG INPUT

ST

FLT

O

K

Controller

I/O Modules

Local Chassis

Remote Chassis

EtherNet/IP Network

IMPORTANT

ControlLogix isolated analog I/O modules support only direct connections

Advertising