Protected bit write – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 102

Advertising
background image

7–15

Communication Commands

Publication 1770Ć6.5.16 - October 1996

protected bit write

Sets or resets individual bits within limited areas of the PLC data
table memory. The access is limited by memory access rungs in the
communication zone of the PLC processor’s ladder diagram
program.

C

CMD

02 STS

TNS

ADDR

R

STS

TNS

CMD

42

DATA (max. 244 bytes)

SET RESET

Up to 60 masks of this form.

DST SRC

SRC DST

DATA

ADDR

SET

RESET

DATA is:

4Ćbyte blocks, each of

which contains a 16Ćbit

address field

Use ADDR to specify the

address of the byte to be

modified in the PLC data

table memory.

Use SET to specify which

bits to set to 1 in the

addressed PLC byte.

Use RESET to specify

which bits to reset to 0 in

the addressed PLC byte.

address field

a set mask

a reset mask

Put the low byte (least

significant bits) of the PLC

address value into the first

byte of the ADDR field.

A 1 in the SET bit position

means to set the

corresponding bit in the

addressed PLC byte to 1.

A 1 in a RESET bit position

means to reset the

corresponding bit in the

addressed PLC byte to 0.

y

A 0 in the SET bit position

means to leave the

corresponding bit in the

PLC byte unchanged.

A 0 in the RESET bit

position means to leave

the corresponding bit in the

PLC byte unchanged.

Important: For some PLC processors, the interface module at the

receiving PLC node executes this command by making
a copy of the addressed PLC byte. It then sets or resets
the appropriate bits and writes the byte back into PLC
memory. At the same time, the PLC processor can
change the states of the original bits in memory.
Because of this, some data bits may unintentionally get
overwritten.

1774ĆPLC

PLCĆ2

PLCĆ3

PLCĆ5

PLCĆ5/250