Download all request (download), Download completed, The processor is being edited – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 94

Advertising
background image

7–7

Communication Commands

Publication 1770Ć6.5.16 - October 1996

download all request (download)

Places a PLC-5 processor in Download mode before downloading a
complete system. A “no privilege” error is returned if the requestor
does not have privilege to place the processor in Download mode.
This error occurs when:

•

the processor is in Run or Remote Run mode (must be in Program
or Remote Program mode)

•

the processor is being edited

•

some other node is already downloading to the processor

CMD

0F

STS

FNC

50

TNS

C

CMD

4F STS

TNS

R

DST SRC

SRC DST

EXT

STS

The EXT STS field may be attached to the reply packet only when there is an error.

download completed

Use after downloading a complete system to place the processor
back in the mode that it was in. (For PLC-5 processors, it returns to
the mode it was in prior to executing download all request.)

CMD

0F

STS

FNC

52

TNS

C

CMD

4F STS

TNS

R

DST SRC

SRC DST

EXT

STS

The EXT STS field may be attached to the reply packet only when there is an error.

•

PLCĆ5

•

PLCĆ5/250

(receive only)

•

PLCĆ5/VME

•

PLCĆ5

•

PLCĆ5/250

(receive only)

•

PLCĆ5/VME

•

SLC 500

•

SLC 5/03

•

SLC 5/04

Advertising