7–7

Communication Commands

Publication 1770Ć6.5.16 - October 1996

download all request (download)

Places a PLC-5 processor in Download mode before downloading a
complete system. A “no privilege” error is returned if the requestor
does not have privilege to place the processor in Download mode.
This error occurs when:

the processor is in Run or Remote Run mode (must be in Program
or Remote Program mode)

the processor is being edited

some other node is already downloading to the processor

CMD

0F

STS

FNC

50

TNS

C

CMD

4F STS

TNS

R

DST SRC

SRC DST

EXT

STS

The EXT STS field may be attached to the reply packet only when there is an error.

download completed

Use after downloading a complete system to place the processor
back in the mode that it was in. (For PLC-5 processors, it returns to
the mode it was in prior to executing download all request.)

CMD

0F

STS

FNC

52

TNS

C

CMD

4F STS

TNS

R

DST SRC

SRC DST

EXT

STS

The EXT STS field may be attached to the reply packet only when there is an error.

PLCĆ5

PLCĆ5/250

(receive only)

PLCĆ5/VME

PLCĆ5

PLCĆ5/250

(receive only)

PLCĆ5/VME

SLC 500

SLC 5/03

SLC 5/04