PLC Addressing

Publication 1770Ć6.5.16 - October 1996

Example: PLCĆ3 logical binary addressing format

E3

1

8

260

0

Data table area = level 1

0

Context = level 2

Section = level 3

File = level 4

Structure = level 5

Word = level 6

level

Byte 1

Byte 2

Byte 3

Byte 4

6 5 4 3 2

1

Byte 5
Byte 6

1 0 1 1 0

0

0 0

flag byte: specifies that the default

values are used for levels 1, 2, and 5

0 0 1 0 0

0

0 0

level 3 (value = 8)

1 1 1 1 1

1

1 1

level 4 delimiter: used to signal that the

level 4 address uses the next two bytes

0 0 0 1 0

0

0 0

level 4 (low byte)

0 0 0 0 0

1

0 0

level 4 (high byte)

0 0 0 0 0

0

0 0

level 6 (value = 0)

= value

260 (decimal)

8 7

bit

5 4 3 2 1

0

7 6

Bytes

Description

1

Flag bits 0, 1, and 4 are set to 0 Ċ default values are used for levels 1,

2, and 5 of the PLCĆ3 address.

Flag bits 2, 3, and 5 are set to 1 Ċ you must specify a value for levels

3, 4, and 6 in the bytes following the flag byte. (Even though the value

of address level 6 is 0, the default value, the last level of a PLCĆ3

address is always specified in the ADDR message packet field.)

2

Address levels are specified lowest level to highest level. Address level

3 is the lowest level that must be specified, so it is specified in the first

byte following the flag byte. It is followed by address level 4, then

address level 6.

3, 4, and 5

The levelĆ4 address is 260 (decimal), which is too large to fit in one

byte. Therefore, byte 3 is a delimiter that contains all 1's (FF hex) and is

used to delimit the 2Ćbyte level 4 address value. The value 260 is then

coded low byte first in bytes 4 and 5.

6

Specifies the levelĆ6 address.