5250 cat. nos – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 171

9–33
Diagnostic Counters
Publication 1770Ć6.5.16 - October 1996
Cat. Nos.
Link
Pages
5250ĆLP1, ĆLP2, ĆLP3, ĆLP4
À
processors
DH+
À
PLCĆ5/250 processors
5250ĆLP1, ĆLP2, ĆLP3, ĆLP4 DH+ Diagnostic Counters
This counter byte Counts the number of
0, 1
Messages sent successfully.
2, 3
Messages received successfully (not counting duplicate messages).
4
Undeliverable messages (message was NAKed or retries were used
up).
5
Response timeouts.
6
NAKs received.
7
Message retries as a result of CRC error, illegal length, DST not
equal to this node, SRC not equal to node that message was sent to,
or timeout.
8
NAKs sent due to memory available.
9
NAKs sent due to message's undefined LSAP.
10
Duplicate messages received.
11
Token pass retries.
12
Packets received that were aborted early.
13
Packets received that had a CRC error.
14
Packets received that had an illegal size (greater than 271 bytes or
less than 3 bytes).
15
Duplicate tokens detected.
16
Recoveries from duplicate node condition.
17
Link dead timeouts.
5250 Cat. Nos.