9–33

Diagnostic Counters

Publication 1770Ć6.5.16 - October 1996

Cat. Nos.

Link

Pages

5250ĆLP1, ĆLP2, ĆLP3, ĆLP4

À

processors

DH+

9-33

À

PLCĆ5/250 processors

5250ĆLP1, ĆLP2, ĆLP3, ĆLP4 DH+ Diagnostic Counters

This counter byte Counts the number of
0, 1

Messages sent successfully.

2, 3

Messages received successfully (not counting duplicate messages).

4

Undeliverable messages (message was NAKed or retries were used

up).

5

Response timeouts.

6

NAKs received.

7

Message retries as a result of CRC error, illegal length, DST not

equal to this node, SRC not equal to node that message was sent to,

or timeout.

8

NAKs sent due to memory available.

9

NAKs sent due to message's undefined LSAP.

10

Duplicate messages received.

11

Token pass retries.

12

Packets received that were aborted early.

13

Packets received that had a CRC error.

14

Packets received that had an illegal size (greater than 271 bytes or

less than 3 bytes).

15

Duplicate tokens detected.

16

Recoveries from duplicate node condition.

17

Link dead timeouts.

5250 Cat. Nos.