Set timeout, Set variables – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 114

7–27
Communication Commands
Publication 1770Ć6.5.16 - October 1996
set timeout
Sets the maximum amount of time that the asynchronous interface
module waits for an acknowledgment to its message transmission.
The setting is expressed as the number of cycles of an internal clock.
(For example, 40 cycles equals 1 second for the 1770-KF2.)
C
CMD
06
STS
FNC
04
TNS
DATA
R
CMD
46
STS
TNS
DST SRC
SRC DST
See the following table for settings and defaults for the module you are
setting. Put the number of desired cycles in the DATA field.
DATA:
Module
Cycles/Sec
Default
1770ĆKF2
40
128 cycles (approx. 3 sec)
1771ĆKE/KF
40
128 cycles (approx. 3 sec)
1771ĆKG
38
38 cycles (approx. 1 sec)
1771ĆKGM
63
63 cycles (approx. 1 sec)
1775ĆKA
40
128 cycles (approx. 3 sec)
1785ĆKE
29
128 cycles (approx. 4.5 sec)
set variables
Sets the maximum ENQs, NAKs, and timeout all at once.
This command is a combination of the set NAKs, set CPU mode, and
set timeout commands.
C
CMD
06
STS
FNC
02
TNS
R
CMD
46
STS
TNS
DATA (3 bytes)
DST SRC
SRC DST
DATA - Put the timeout setting in the first byte, the NAKs setting in the second byte, and the
ENQs in the third byte.
•
PLCĆ2
•
PLCĆ3
•
PLCĆ5
•
PLCĆ2
•
PLCĆ3
•
PLCĆ5