Remote sts and ext sts codes, Dh485 ext sts codes – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 132

Advertising
background image

8–5

Message Packet Status Codes (STS, EXT STS)

Publication 1770Ć6.5.16 - October 1996

DH485 EXT STS Codes

Hex Code

Explanation

07H

Insufficient memory module size (0000h is returned)

0BH

Access denied, privilege violation

0CH

Resource not available or can not do

0EH

CMD can not be executed

12H

Invalid parameter

14H

Failure during processing

19H

Duplicate label

1AH

File open by another node + owner's local node address, 1 byte

1BH

Program owned by another node + program owner's local node

address, 1 byte

For these codes

See

remote STS codes from a PLCĆ2 or 1774ĆPLC processor

section below

remote STS and EXT STS codes from a PLCĆ3 processor

page

8-6

Remote STS Codes from a PLCĆ2 or 1774ĆPLC Processor

STS codes that may be sent from your PLC-2 (or 1774-PLC)
processor to your computer include:

STS Code

Explanation

10

The command message (command code, subĆcommand code, size of the

command or requested reply size) was incorrect.

20

There are verification errors within the host PLC processor.

30

A condition exists at the PLCĆ2 processor that requires manual intervention,

such as:

the cable between the module and the processor is unplugged

the processor is faulted

40

A communication error on the cable or on backplane access between the

module, and the processor has aborted message execution.

50

An attempt to access an illegal address in the PLCĆ2 processor has aborted

message execution. Illegal access may result from access outside:

the data table as defined by the PLCĆ2

a memory access window (protected commands only)

Illegal access may also mean that the PLCĆ2 processor has attempted to

communicate with a PLCĆ3, PLCĆ5, or an SLC 500 processors that does not

have the proper compatibility file.

60

Execution of a command at the PLCĆ2 processor is disabled by a switch

option.

70

The PLCĆ2 processor is in Program or Remote Program mode, or the 1771ĆKA

is in Download mode. Alternatively, this code can also mean that the PLCĆ2

processor is not in Program or Remote Program mode.

80

Execution of protected commands at the PLCĆ2 processor is inhibited because

its PROG light is on.

The error sets the remote error bit for the associated rung.

Remote STS and

EXT STS Codes

Advertising