Plcć5 physical addressing – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 231

13–16
PLC Addressing
Publication 1770Ć6.5.16 - October 1996
PLCĆ5 Physical Addressing
PLC-5 processors use physical addresses that are related to logical
addresses by means of pointers. Since no two PLC-5 systems are
configured identically, the pointers are not fixed. Therefore, there is
no algorithm for converting logical to physical PLC-5 addresses.
A PLC-5 physical address goes in the 4-byte field labelled PLC-5
PHYSICAL ADDR in the PLC-5 physical read or write command
message packets. A physical address is made of 24 bits. These bits
are inserted in the message packet physical address field as follows
(bits are labelled A1 to A24 respectively):
Function (FNC) Field
First byte
A8
A7
A6
A5
A4
A3
A2
A1
Second byte
A16
A15
A14
A13
A12
A11
A10
A9
Third byte
A24
A23
A22
A21
A20
A19
A18
A17
Fourth byte
0
0
0
0
0
0
0
0
Size Field
For example, to address a command message to physical word
address 12,200 decimal (002FA8 hex), use the following binary code
in the address field:
First byte
1
0
1
0
1
0
0
0
(value A8 hex)
Second byte
0
0
1
0
1
1
1
1
(value 2F hex)
Third byte
0
0
0
0
0
0
0
0
(values 00 hex)
Fourth byte
0
0
0
0
0
0
0
0
(always 00 hex)
The recommended procedure for uploading or downloading PLC-5
memory is to begin at physical address 0000 and proceed
sequentially to the end of memory. Therefore, each successive
physical read or write begins at the next physical address after the
one where the previous command stopped. Since a single physical
read or write command can transfer only about 120 words of data,
it takes many commands to upload or download the entire PLC-5
memory.