8–9

Message Packet Status Codes (STS, EXT STS)

Publication 1770Ć6.5.16 - October 1996

Command

Explanation

STS Code

EXT STS Code

PLCĆ3 physical reads

-

10

There is more than one byte of data after the byte

address.

The number of bytes to read:

- is an odd number.

- equals zero.

- is greater than the maximum allowed in a reply

packet (244).

The sum of packet offset and size of data in words

is greater than 65,535.

The sum of packet offset and size of data in words

is greater than the total transaction size.

-

30

The local PLCĆ3 interface module has executed a

shutdown request.

-

40

A backplane error (memory parity, timeout, or

disconnect) has occurred.

-

70

The local PLCĆ3 processor is in Program mode.

1

F0

There was an error converting the block address

(major section > 63, context > 15, section > 15).

2

F0

Three or fewer addressing levels specified for a

PLCĆ3 word address.

3

F0

The conversion of a file address to a block address

resulted in more than nine addressing levels.

4

F0

The symbolic address was not found.

5

F0

The symbolic address is zero or more than eight

bytes.

6

F0

The file was not found.

DST address does not have enough levels to

specify a PLCĆ3 word (for wordĆrange reads) or a

file (for file reads).

The PLCĆ3 address specifies more levels than

required.

The word specified by the PLCĆ3 address does not

exist.

7

F0

Any of the DST words in the DST file do not exist.

For a file read, the SRC and DST files are not the

same size.

8

F0

The file size decreased between packets of a

multiĆpacket transaction and became too small for

the total transaction.

9

F0

You tried to read or write past the end of a file.

A

F0

Start bytes.