Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 181

Advertising
background image

10–10

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

Bytes

Description

Contents

Bits

10

Settings of the option switches on the

1771ĆKGM Module

1

g

p

node interface module.

0 = second module

1 = first module

2

0 = accept physical/unprotected reads and writes disabled

1 = accept physical/unprotected reads and writes enabled

4, 3, 0

Binary values:

Value

Parity

Error

Embedded

Protocol

Check

Responses

p

001

none

BCC

disabled

halfĆduplex

101

even

BCC

disabled

halfĆduplex

011

none

CRC

enabled

halfĆduplex

5 - 7

Asynchronous link baud rate

0 = 110 bps

1 = 300 bps

2 = 600 bps

3 = 1200 bps 4 = 2400 bps 5 = 4800 bps

6 = 9600 bps 7 = 19200 bps
1774ĆKA Module

0

0 = Unprotected commands enabled

1 = Unprotected commands disabled

1

not used

2

0 = Physical writes enabled

1 = Physical writes disabled

3

0 = Transmission of unprotected commands enabled

1 = Transmission of unprotected commands disabled

4

0 = DH port B is connected

1 = DH port A is connected

5

0 = PLC outputs held in last state

1 = PLC outputs turned off

6 - 7

0 = 57,600 bits per second DH baud rate

1 = undefined

2 = undefined

3 = undefined
1770ĆKF2 Module

0 - 1

0 = 57,600 bits per second Data Higway or Data Highway

Plus baud rate

1 = undefined

2 = undefined

3 = undefined

2

Not used

3 - 7

Logical complement of the state of option switch SWĆ2,

switches 1 through 5

Advertising