Word range write (write block), Write bytes physical (physical write) – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 122

Advertising
background image

7–35

Communication Commands

Publication 1770Ć6.5.16 - October 1996

word range write (write block)

Writes to a word or file starting at a specified address. A special
case of this command is the single-word write, where the data field is
only one word long.

CMD

0F

STS

FNC

00

TNS

C

CMD

4F

STS

R

DST SRC

SRC DST

Packet

Offset

PLC system address

Total

Trans

Data (max. 240 bytes -

the PLC address field)

TNS

EXT

STS

The EXT STS field may be attached to the reply packet only when there is an error.

For this processor

The starting address can be a

PLCĆ3

word symbol, file symbol plus a word offset, or a block address.

The starting address must point to a word in a file.

PLCĆ5

logical binary address or a logical ASCII address of up to 51

bytes.

write bytes physical (physical write)

Performs a download only after receiving a reply that the download
(
or upload) all request has been successfully performed.

CMD

0F

STS

FNC

18

TNS

C

CMD

4F

STS

TNS

R

DST SRC

SRC DST

EXT

STS

PLCĆ5 phys. address

A

PLCĆ5 physical address - contains the address you are writing to.
A - Up to 238 bytes can be written with a single command (low byte of the word first).

(Must be an even number of data bytes.)

The EXT STS field may be attached to the reply packet only when there is an error.

PLCĆ3

PLCĆ5

PLCĆ5

PLCĆ5/VME