background image

4–10

Using Full-duplex Protocol to Send and Receive Messages

Publication 1770Ć6.5.16 - October 1996

These transfer diagrams show events that occur on various
interfaces. Time is represented as increasing from the top of the
diagram to the bottom. Link-layer data bytes are represented by
“xxxx” and corrupted data by “???”.

For this diagram

See page

normal message transfer

4-10

message transfer with NAK

4-11

message transfer with timeout & ENQ

4-12

message transfer with reĆtransmission

4-13

message transfer with message sink full

4-14

message transfer with NAK on reply

4-15

message transfer with timeout and ENQ for the reply

4-16

message transfer with message source full on the reply

4-17

Normal Message Transfer

In this transfer:

•

t

he transmitter sends the data to the receiver

•

the sink sends a “not full” message

•

the receiver sends the data to the sink and sends a DLE ACK to
the transmitter

•

the transmitter tells the source that the data was delivered

•

reply is successfully returned

xxxx

not full

OK

OK

xxxx

not full

xxxx

DLE STX xxxx DLE ETX BCC/CRC

DLE ACK

DLE STX xxxx DLE ETX BCC/CRC

DLE ACK

Source

Transmitter

Link

Receiver

Sink

command

reply

(sometime later ...)

FullĆduplex Protocol

Diagrams